Serie UPS5000-E (40 kVA-200 kVA)
El UPS5000-E utiliza la redundancia modular y la doble conversión en línea. Ofrece alta eficacia y densidad de alimentación. El UPS ofrece soluciones confiables, económicas, inteligentes y fáciles de usar. Puede suministrar energía de alta calidad a centros de datos, salas de servidores, sistemas de seguridad y cargas clave (como equipos de fabricación automáticos) medianos y grandes. El UPS5000-E ofrece protección de energía de 40 kVA/kW, 80 kVA/kW, 120 kVA/kW, 160 kVA/kW o 200 kVA/kW, lo que elimina el impacto de las fallas eléctricas en los equipos del cliente.
Reliable
- Wide input voltage and frequency range: 138-485Vac, 40-70Hz
- 5kA lighting protection design on input port to reduce lightning-related failure rate
- Redundant design and hot-swappable controllers, which improve the reliability of the whole system
Efficient
- High efficiency at low load rate: 95%@20% load; 96%@40% load
- Intelligent hibernation technology to improve operation efficiency and reduce the UPS power loss efficiently
Convenient
- Hot swappable power modules, control modules, and bypass modules make module replacement time close to 0, which facilitates capacity expansion and maintenance
- High power density of up to 40kVA/3U, and only 0.5 square meters taken up
- High output power factor of up to 1 and 25% more load driven
- The 7-inch colored LCD in standard configurations
Intelligent
- Intelligent battery management to extend battery service time by 50%
- Built-in SNMP card and HUAWEI Neteco 1000 software, easy to manage remotely
- Various optional components to meet customized demands
Model
|
UPS5000-E-120K-F120
|
UPS5000-E-200K-F200
|
UPS5000-E-320K-F320
|
Rated Capacity
(kVA / kW)
|
40/80/120
|
40/80/120/160/200
|
40/80/120/160/200/240/280/320
|
The Number of Power Modules
|
1/2/3
|
1/2/3/4/5
|
1/2/3/4/5/6/7/8
|
Height×Width×Depth
|
2000 mm × 600 mm × 850 mm
|
Weight
|
227-293 kg
|
227-359kg
|
227-480kg
|
Input
|
Input Wiring
|
3Ph+N+PE
|
Rated Voltage
|
380/400/415 V AC
|
Input Voltage Range
|
138-485 V AC; 305-485 V AC for 100% load; 305V-138 V AC for 100%-40% load (derating linearly)
|
Input Frequency Range
|
40-70 Hz
|
THDi (Total Harmonic Distortion of Input Current)
|
THDi<3% (for linear load); THDi<5% (for nonlinear load)
|
Input Power Factor
|
0.99
|
Bypass Voltage
|
380/400/415 V AC
|
Bypass Input Wiring
|
3Ph+N+PE
|
Bypass Frequency Range
|
50/60±6 Hz
|
Battery Voltage
|
360-480 Vdc
|
Output
|
Output Wiring
|
3Ph+N+PE
|
Output Voltage
|
380/400/415 V AC±1%
|
Output Frequency
|
Tracking the bypass input (online mode); 50/60 Hz±0.1% (battery mode)
|
Waveform
|
Sine wave; THDv<1% for 100% linear load and THDv<3% for 100% nonlinear load
|
Output Power Factor
|
1
|
System Efficiency
|
96%
|
Overload Capacity
|
Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minutes
Bypass: 135% overload for long term; >1000% overload for 100 ms
|
Environment
|
Operating Temperature
|
0-40℃
|
Storage Temperature
|
-40-+70℃
|
Relative Humidity
|
0%-95% (non-condensing)
|
Operating Altitude
|
1000 m; above 1000 m, derating 1% for each additional 100 m
|
Audible Noise
|
<65dB
|
<68dB
|
Others
|
Certifications
|
EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc.
|
Communication Interfaces
|
Dry Contacts, RS485, SNMP
|
The main optional components of UPS5000-E are shown in the table below:
Item
|
Detail
|
Communication card
|
-- Dry contact extended card
-- Backfeed protection card
|
Power distribution
|
-- Input power distribution cabinet
-- Output power distribution cabinet
-- Battery switch box
-- Battery circuit breaker (BCB) box
|
Battery Management kit
|
-- Battery monitoring unit
-- Battery ground fault detector
|
Environment
|
-- Ambient temperature and humidity sensor
-- Battery temperature sensor
|
Mechanical kit
|
-- Top outlet kit (for UPS5000-E-120K-F120 and UPS5000-E-120K-F200)
-- Top entry cabinet (for UPS5000-E-320K-F320)
-- IP21 component
-- Antiseismic kit
|