Type
|
TP48200B
|
TP48300B
|
TP48600B
|
System specification
|
Dimension
|
2000mm(H)×600mm(W)×600mm(D)
|
1600mm(H)×600mm(W)×400mm(D)
|
Weight
|
≤100kg(without rectifiers and batteries)
|
≤100kg(without rectifier modules)
|
Rated capacity
|
200A(can configure 2~4 rectifiers)
|
300A(can configure 2~6 rectifiers)
|
600A(can configure 2~12 rectifiers)
|
Cooling mode
|
Natural cooling
|
Maintenance mode
|
Front access maintenance
|
Cabling mode
|
Top inlet and top outlet
|
Top or Bottom inlet and outlet
|
Installation mode
|
Antistatic floor installation or ground installation
|
User space/ built-in batteries
|
0~16U user space
2~4 groups of battery
|
N/A
|
Protection level
|
IP20
|
Environmental specification
|
Operating temperature
|
-10~+45℃
|
-10~+50℃
|
Operating humidity
|
5%~95%(non-condensing)
|
Altitude
|
0~4000m (at the altitude from 2000m to 4000m, the temperature declines by 1ºC for each increase of 200m in altitude)
|
AC distribution
|
AC input
|
One phase three line(L,N,PE);
Three phase four line (L1,L2,L3,N);
Three phase five line(L1,L2,L3,N,PE);
110V dual live wire(L1, L2)
|
Three phase four line (L1,L2,L3,N);
Three phase five line(L1, L2, L3, N, PE);
Single phase(L, N)
|
Three phase four line (L1,L2,L3,N);
Three phase five line(L1, L2, L3, N, PE);
|
AC input voltage
|
85~300VAC, rated: 220VAC
|
AC input frequency
|
45~66Hz, rated: 50Hz/60Hz
|
SPD for AC input
|
Standard surge discharge current: 20kA, 8/20µs
Maximum surge discharge current: 40kA, 8/20µs
|
DC distribution
|
Output voltage
|
42~58VDC, default value: 53.5VDC
|
maximum output power
|
12000W
|
18000W
|
36000W
|
Battery branch
|
125A x 4 (or 2) MCB
|
250A×2 (fuse)
|
500A×2 (fuse)
|
BLVD
|
32A x 2 MCB, 16A x 3 MCB, 10A x 1 MCB
|
32A×2 MCB, 10A×2 MCB ( 4×63A MCB installation position reserved)
|
MCB:63A×2, 32A×2, 10A×2 ( 2× 63A MCB installation position reserved)
|
LLVD
|
80A x 2 MCB, 32A x 1 MCB, 20A x 2 MCB
|
100A×3(NT00 fuse), 32A×1 MCB; 10 reserved installation position (maximum 100A×3 NT00 fuse and maximum 63A×7 MCB)
|
160A×3(NT00 fuse), 100A×2(NT00 fuse), 63A×2 MCB, 32A×3 MCB, 10A×2 MCB; 5 installation position reserved (maximum 160A×1 NT00 fuse and 63A×4 MCB)
|
Rectifier module
|
Efficiency
|
>96%
|
Input voltage
|
85~300VAC, rated: 220VAC
|
Monitoring unit
|
Sensor ports
|
TEM_HUM, WATER, GATE,SMOKE,
BTEMP
|
SMOKE, TEM_BAT, TEM2
|
Boolean value
input ports
|
6 branches
|
7 branches
|
Alarm output
|
8 branches
|
5 branches
|
Communication port
|
RS232/485, FE
|
RS485/RS232
Ethernet interface(available with optional SNMP card)
|