Página Anterior!

Prompt

No ha iniciado sesión o no esta autorizado!

Página Anterior

Suministro de energía en exterior

Los productos de alimentación de la serie TP48200A convierten corriente de entrada de CA en corriente de salida de -48 VCC. Son ampliamente utilizados en entornos de exterior de DBS, BTS, y DBS más BTS. Los productos se centran en funciones como seguridad, eficiencia energética, confiabilidad, integración flexible, y brindan soluciones de energía confiables a los sitios de exterior.

Suministro de energía en exterior_banner

  • Suministro de energía en exterior_banner
  • Extra wide range of AC input voltage from 85V to 300V per phase
  • High rectifier efficiency over 96% helps to save energy
  • Excellent rectifier dormancy function helps to increase system efficiency
  • Wide working temperature range of rectifier from -40℃ to 75℃
  • Rectifier MTBF≥ 500,000 hours
  • Online-swappable rectifier provides easy installation and maintenance
  • Intelligent battery management and protection helps to prolong battery lifespan
  • Anti-reverse connection of battery polarity function
  • Support site environment monitoring and remote management through dry contact, serial interface or network interface
  • Intelligent control module with LCD provides visible monitoring
  • Thorough alarms and protection against failures
  • E- label function provides online equipments management over entire network
  • Highly integrated cabinet with battery and main equipments inside makes quick installation
  • Well environmental adaptability with IP55 class protection



Integrated Power Cabinet Specifications

Type TP48200A-H15A3 TP48200A-H15A5 TP48200A-D15A1
System specification Dimension 1500mm(H)*650mm(W)*650mm(D)(excluding base)
Weight <120Kg (excluding rectifier and battery)
Rated capacity 200A
Cooling mode Heat exchanger for equipment cabin, direct ventilation for battery cabin Direct ventilation
Maintenance In front, supporting modular replacement
Cabling mode Cable outlet from the bottom of the cabinet
Protection level Equipment cabin: IP55, Battery cabin: IP45 IP55
Environment specification Operating temperature -10~+45ºC -40~+45ºC -10~+45ºC
Operating humidity 5%~95%(non-condensing)
Altitude 0~4000m (at the altitude from 2000m to 4000m, the temperature declines by 1ºC for each increase of 200m in altitude)
AC distribution Input mode Single phase/ Three phase
Input voltage 85~300VAC, rated: 220VAC
Input frequency 45~65Hz, rated: 50Hz/60Hz
Input distribution 1×63A/3P MCB
Output distribution 2 ×16A MCB
SPD for AC input Class C surge protection Standard surge discharge current: 20kA, 8/20µs Maximum surge discharge current: 40kA, 8/20µs
DC distribution Output voltage 42~58VDC, default value: 53.5VDC
SPD for DC output Differential mode: 10kA, 8/20µs; Common mode: 20kA, 8/20µs
Output power 11600W(normal efficiency) /12000W(high efficiency)
Battery branch 2x125A MCB
BLVD 2×16A MCB
LLVD 2× 63A, 2×32A MCB
Rectifier module Efficiency >96%
Input voltage 85~300VAC, rated: 220VAC
Monitoring unit Communication RS485/232, FE
Sensor battery temperature, door, environment temperature, environment humidity , smoke, water, 6 battery voltage check points
Dry contact Eight maximum, alarm signal information can be defined
Digital signal detection Eight, one for AC SPD monitor, one for DC SPD monitor, six spared


Split Type Cabinet Specifications

Type TP48200E-H09A1 TP48200E-D09A1 TBC300A-DCA1 TBC300A-TCA1
System specification Dimension 900mm(H)*650mm(W)*650mm(D)(excluding base)
Weight <70Kg (excluding rectifier, battery)
Rated capacity 200A 2 group 150AH batteries
Cooling mode Heat exchanger Direct ventilation Direct ventilation TEC
Maintenance In front, supporting modular replacement
Cabling mode Cable outlet from the bottom of the cabinet
Installation mode Installed on 19-inch rack N/A
Protection level IP55 IP34 IP55
Environment specification Operating temperature -40~+45ºC -10~+45ºC
Operating humidity 5%~95%(non-condensing)
Altitude 0~4000m (at the altitude from 2000m to 4000m, the temperature declines by 1ºC for each increase of 200m in altitude)
AC distribution Input mode Single phase/ Three phase -48V
Input voltage 85~300VAC, rated: 220VAC N/A
Input frequency 45~65Hz, rated: 50Hz/60Hz N/A
Input distribution 1×63A/3P MCB N/A
Output distribution 2 ×16A MCB N/A
SPD for AC input Class C surge protection Standard surge discharge current: 20kA, 8/20µs Maximum surge discharge current: 40kA, 8/20µs N/A
DC distribution Output voltage 42~58VDC, default value: 53.5VDC N/A
SPD for DC output Differential mode: 10kA, 8/20µs; Common mode: 20kA, 8/20µs N/A
Output power 11600W(normal efficiency) /12000W(high efficiency) N/A
Battery branch 2x125A MCB N/A
BLVD 16A×2, 10A×1 MCB N/A
LLVD 63A×2, 32A×2 MCB N/A
Rectifier module Efficiency >96% N/A
Input voltage 85~300VAC, rated: 220VAC N/A
Monitoring unit Communication RS485/RS232, FE RS485
Sensor battery temperature, door, environment temperature, environment humidity , smoke, water sensor, 6 battery voltage check points smoke , water
Dry contact Eight maximum, alarm signal information can be defined inside temperature, fan alarm, door open alarm
Digital signal detection Eight, one for AC SPD monitor, one for DC SPD monitor, six spared N/A


Outdoor power : including cabinet, rectifier, battery, sensor


Cabinet: northern or southern type selected by climate


Rectifier: the number is confirmed by load power, battery power and rectifier type


Sensor: door sensor, battery temperature sensor are must be configured, smoke, water, environment temperature & humidity sensor are optional.


Battery: the number is determined by load power and backup time.


Notes: Battery capacity, rectifier number and temperature control type and application environment determine the cabinet type.