Saving TCO
Industry-leading fast charging technology, up to 0.8C charging current, ensuring battery fully charged when grid is on. D.G can be removed, therefore remarkably saving diesel and maintenance.
Leading ESS-A technology, saving OPEX and protecting investment
- Up to 0.8C charging current, very fast charged;
- ESS-A has long cycle life in high temperature environment, 3500 cycles @ 85% DOD, 35℃;
- Small size and light weight, helps to reduce transportation expenses;
- Support remote parameter management and setting ,support parameter series renewal;
- Supports real-time statistics and management of key parameters such as solar production, load consumption, load current, system voltage, battery current and total energy production;
- Support history data query and KPI index report and analysis;
- Anti-theft design.
High Stability and Reliability
Original site batteries can be reserved for spare use, which improves stability and reliability.
Fast deployment, saving site construction time
- Small dimension and volume, less land surface, easy to deploy, easy to install;
- Integrated design, facilitating engineering work such as operation, cabling.
Value-added services
- E-tag for remote property management;
- Electric expenditure calculation;
- Refuel reminding;
Smooth evolution
- Modular design;
- Easy expansion;
- System support smooth evolution of different hybrid power solutions(solar solution, Solar-Grid hybrid solution, etc.).
PowerCube-G
|
G302A
|
Configuration
|
|
Power Supply Unit Capacity (A)
|
50A*5
|
Cooling Method of Integrated Inverter & Converter
|
Heat exchange
|
Cooling Method of Energy Storage System
|
DC-Air conditioner
|
Energy Storage System Type
|
ESS-F
|
Energy Storage System Capacity (KWh)
|
31.2
|
Power distribution
|
Secondary load (-48v)
|
1*125A (MCB),2*63A (MCB)
|
Primary load (-48v)
|
2*32A (MCB), 1*16A (MCB)
|
Physical Specifications
|
|
Dimensions (W x D x H) (mm)
|
770×1250×1825
|
Weight (Kg)
|
<1243
|
Customer Equipment Space/ Heat Consumption
|
11U (front 3U, back 8U) / 350W
|
Power Supply Unit Efficiency
|
Up to 97%
|
Protection Level
|
Integrated Inverter & Converter System
|
IP55
|
Energy Storage System
|
IP55
|
Operating Conditions
|
|
Operating Temperature
|
-20~+50℃
|
Storage Temperature
|
-40~+70℃
|
Operating Humidity
|
5%~95%
|
Operating Altitude
|
0~4,000m (derated when >2,000m)
|
Wind-resistant Level
|
≤50m/s
|
Functions
|
|
|
All-in-one Control Design
|
●
|
Controller Software Online Upgrading
|
●
|
LLVD & BLVD
|
●
|
Surge Protection Design for Signal & Power Interface
|
●
|
Statistics on Num of Charge/Discharge, Sum of Discharge Capacity
|
●
|
Real Time Monitor Voltage, Current, Temperature of Energy Storage System
|
●
|
IP,GPRS, SMS Networking
|
¡
|
Real-time Data Monitoring
|
¡
|
Historical Data & Alarms Tracking System
|
¡
|
KPI Performance Statistics
|
¡
|
Remote Configuration & Operation
|
¡
|
Remote Login Via Website
|
¡
|
Remark : "●"Mandatory, "○"Optional,"-" None
EPS(Energy Plant System):
EPS (Energy Plant System) is the power source, including commercial grid power, solar power and D.G power.
ICC (Integrated Controller and Converter):
The ICC consists of a cabinet, a temperature system, ECC500, an integrated distribution unit (IDU), power supply unit (PSU). The cabinet has both the front and back doors.
ESS (Energy Storage System):
The ESS consists of batteries and a cabinet which are integrated together with ICC inside one cabinet.
OSS (Operation Support System):
The OSS is composed of NMC (NetEco), Network(GPRS/IP), ECC500 etc, ECC500 collects power and environment parameter through serial port and I/O port and then communicates with NMC through network. It supports data collection, data transmission and data display.