Basic type
The basic type of IDS2000-S is mainly used in ordinary buildings with ventilation function and the ambient temperature is between 5 and 30 ℃.
Items
|
Specifications
|
Single cabinet dimensions (H*W*D)
|
2000mm*600mm*1100mm
|
IT rated power
|
IT rated power≤4.5kW
|
Power supply
|
220V、230V、240V/50(60)Hz;208V(double live wire)/50(60)Hz
|
External interface
|
Local standard power interface
|
Operation condition
|
Temperature of 5℃ to 30℃, relative humidity of 10% to 90%, altitude of 0m to 3000m
|
Structure
|
Single front door and double rear doors with 110 degree Opening angle
|
Heat dissipation
|
The speed of intelligent fans at top of the cabinet is adjusted in real time according to the temperature in order to save energy.
|
Air flow
|
70% door open ratio, Front-back air flow pattern, Optional cooling module at the top of cabinet
|
Power distribution
|
Various efficient UPSs with different backup time for option, C-class lightning protection and manual maintenance bypass UPS
|
Monitoring system
|
Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.
|
Installation type
|
Coupled with wheels and leveling feet
|
Typical Configuration
|
Main Cabinet
User Space
|
Network Cabling
Cabinet User Space
|
Battery
Cabinet
|
UPS
|
Battery
Backup Time
|
Main Cabinet with UPS
|
25U
|
×
|
×
|
√
|
30min
|
Main Cabinet with UPS + Network Cabling Cabinet
|
25U
|
42U
|
×
|
√
|
30min
|
Main Cabinet with UPS* + Battery Cabinet
|
31U
|
×
|
√
|
√
|
30min/1h/2h/4h/8h optional
|
Main Cabinet with UPS * + Network Cabling Cabinet + Battery Cabinet
|
31U
|
42U
|
√
|
√
|
30min/1h/2h/4h/8h optional
|
Note:
* "× "stands for no configuration, "√" stands for standard configuration. Switch, router or sever are not mandatory, and will be provided by customers.
Main cabinet standard configuration: One set of PDU, monitoring module, smoke detector, temperature and humidity sensor, water sensor, door magnetic switch.
Network cabling cabinet standard configuration: One set of PDU, smoke detector and door magnetic switch.
Battery cabinet standard configuration: One set of smoke detector and door magnetic switch.