UPS:
UPS5000-E-200K-F200:contains 40kVA/40kW,80kVA/80kW,120kVA/120kW,160kVA/160kW,200kVA/200kW five configurations,separately contains 1、2、3、4、5 power modules,supporting three phase input ,three phase output;
The number of modules and racks accord to the load power consumption, redundancy needs.
Communication cards:(standard)
Dry contact card:Enables the UPS to manage the battery system (including the external battery switch and battery detector), communicate with the PC, provide alarm signals for external devices, and shut down devices remotely in emergencies.
Monitoring Interface Card:The monitoring interface cards include the FE port(supporting SNMP)、RS485(network management port)、Dry contact port.
Battery:
Configuring battery according to the load and the battery running time
Optional Components:
Parallel Options:
- Parallel cable:The parallel cable connects UPSs in parallel
- BSC cable:The BSC cable transmits bus synchronization signals in a dual-bus system.
PDC Options:
- Input power distribution cabinet:The input PDC uses one 4-pole 630 A input AC transfer switch (ATS) and two 3-pole 400 A mould case circuit breakers (MCCBs) respectively for mains and bypass outputs. The input PDC measures and displays electrical parameters, such as the three-phase input voltage, current, and power factor. The input PDC provides dry contacts to report the status of circuit breakers and a three-phase power indicator to display the power status.
- Output power distribution cabinet:The output PDC uses two 4-pole 400 A input MCCBs and one 3-pole 630 A maintenance bypass circuit breaker. The output PDC measures and displays electrical parameters, such as the three-phase input voltage, current, and power factor. The output PDC provides dry contacts to report the status of circuit breakers and a three-phase power indicator to display the power status.
Other options
- Dry contact extended card: The dry contact extended card provides extended monitoring ports: five groups of relay output ports and five groups of input ports. Backfeed protection card:The backfeed protection card detects mains and bypass backfeed and provides protection.
- Backfeed protection card: The backfeed protection card detects mains and bypass backfeed and provides protection.
- Battery switch box: The battery switch box controls the connection between battery strings and the UPS, and provides overload and short-circuit protection
- Battery circuit breaker (BCB) box: The BCB box controls the connection between battery strings and the UPS when multiple battery strings are connected in parallel.
- Top outlet kit: If you need to install the cabinet against the wall, install the top outlet kit to meet heat dissipation requirements.
- IP21 component: The IP21 component prevents water from dropping into the cabinet, and protects the cabinet to IP21.
- Antiseismic kit: The antiseismic kit reinforces the cabinet so that the cabinet meets the requirements of 9 degree seismic fortification intensity.
- Battery detector: The battery detector monitors battery voltages and temperatures and battery string charge and discharge currents, and communicates with the PC over Modbus
- Battery grounding failure detector: The battery grounding failure detector detects battery grounding failures and sends alarm signals when the ground leakage current exceeds the specified value.
- Temperature and humidity collection board: Test the temperature and humidity of UPS.
- Temperature and humidity collection: Test the temperature of battery room.