| Model
|
UPS5000-E-120K-F120
|
Rated Capacity
(kVA / kW)
|
40
|
80
|
120
|
| The Number of Power Modules
|
1
|
2
|
3
|
| Dimensions
(H×W×D)
|
2000 mm × 600 mm × 850 mm
|
| Weight
|
227 kg
|
260 kg
|
293 kg
|
| Input
|
| Input Wiring
|
3Ph+N+PE
|
| Rated Voltage
|
380/400/415 V AC
|
| Input Voltage Range
|
138-485 V AC; 305-485 V AC for 100% load; 305V-138 V AC for 100%-40% load (derating linearly)
|
| Input Frequency Range
|
40-70 Hz
|
| THDi (Total Harmonic Distortion of Input Current)
|
THDi<3% (for linear load); THDi<5% (for nonlinear load)
|
| Input Power Factor
|
0.99
|
| Bypass Voltage
|
380/400/415 V AC
|
| Bypass Input Wiring
|
3Ph+N+PE
|
| Bypass Frequency Range
|
50/60±6 Hz
|
| Battery Voltage
|
360-480 Vdc
|
| Output
|
| Output Wiring
|
3Ph+N+PE
|
| Output Voltage
|
380/400/415 V AC±1%
|
| Output Frequency
|
Tracking the bypass input (online mode); 50/60 Hz±0.1% (battery mode)
|
| Waveform
|
Sine wave; THDv<1% for 100% linear load and THDv<3% for 100% nonlinear load
|
| Output Power Factor
|
1
|
| System Efficiency
|
96%
|
| Overload Capacity
|
Inverter: 110% overload for 60 minutes; 125% overload for 10 minutes; 150% overload for 1 minutes
Bypass: 135% overload for long term; >1000% overload for 100 ms
|
| Environment
|
| Operating Temperature
|
0-40℃
|
| Storage Temperature
|
-40-+70℃
|
| Relative Humidity
|
0%-95% (non-condensing)
|
| Operating Altitude
|
1000 m; above 1000 m, derating 1% for each additional 100 m
|
| Audible Noise
|
<65dB
|
| Others
|
| Certifications
|
EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; Rohs, Reach, WEEE, etc.
|
| Communication Interfaces
|
Dry Contacts, RS485, SNMP
|