NetCol8000-A Series(Air-cooled In-room)

NetCol8000-A is an air cooled in-room precision air conditioner developed by Huawei. It is composed of indoor and outdoor units. The indoor unit is configured with scroll compressors, large surface evaporators, EC fans (optional), infrared humidifiers and PTC electric heaters. Cooling capacity ranges are 50kW and 100kW. It is usually deployed around the free space of a data center, and can be installed against the wall to provide 100% front access maintenance. The fan can be installed beneath the raised floor to further improve air supply efficiency. NetCol8000-A is a highly efficient and reliable solution, which is also simple & convenient to install and maintain, contributing to building next generation green data centers.


Efficient

  • CFD simulation and field synergy design help reduce air pressure drop by 30% and increase cooling density by 15%.
  • Unique energy saving logic: for single unit, the partial load EER is increased by 26%; for multi units system, energy saving is increased by over 30% with the features of non-conflicting, collaborating and optimized efficiency operation.


Reliable

  • Independent dual circuits design: the fault of single system will not affect the other one.
  • Group control realizes alternative operation and hot backup to avoid conflicting operations among units and ensure the stable running of IDC.
  • Refrigerant leakage and anti-freezing protection: the unit will be switched off while refrigerant leaked, to prevent evaporator frosting or freezing


Convenient

  • Independent dual modular design eliminates brazing work for on-site unit disassembly and reduces the requirement on dimensions of elevator and doors.
  • 100% front maintenance: side-by-side or against-the-wall installations are available to achieve the lowest footprint and maintenance space requirement throughout the industry.
  • Expert management system clearly presents the fault cause and maintenance countermeasures instantly.


NetCol8000-A Technical Specification:

Model Unit NetCol8000-A 050D NetCol8000-A 100D
Type Air-cooled
Air Discharge Direction Bottom
EC fan Total Cooling Capacity kW 50.0 100.0
Sensible Cooling Capacity kW 46.8 93.5
Air Flow m3/h 14,000 28,000
AC fan Total Cooling Capacity kW 50.0 100.0
Sensible Cooling Capacity kW 45.0 90.0
Air Flow m3/h 13,250 26,500
Power Supply V/Ph/Hz 380-415/3/50
Refrigerant R410A
Electric Heating Capacity kW 6 12
Humidifying Capacity kg/h 7 10
Full Load Current EC fan A 38.0 76.0
AC fan A 42.0 84.0
Dimensions: W×D×H mm 1140×890×1980 2280×890×1980
Net Weight kg 415 830


Notes:


  • Nominal cooling condition: return air dry bulb temperature 24C; RH50%; condensing temperature 45C.
  • Data are subject to change without prior notice


Outdoor Condenser Unit Technical Specification:

Model Unit NetCol500-A072M NetCol500-A088M
Power Supply V/Ph/Hz 380-415/3/50
Fan Quantity PCS 2
Net Weight kg 150 200
Liquid Pipe Diameter in 5/8in
Gas Pipe Diameter in 7/8in
Full Load Current A 3.15 6.25
Dimensions: W×D×H mm 2180×1094×1100 2410×1270×1265