UPS8000-D Series (200-600 kVA)

UPS8000-D series is an online sine-wave double-conversion UPS which features high performance. It is designed for large- and medium-sized computer rooms (for example, network computer rooms in the finance, communications, insurance, railway, medical, and mining industries, enterprises, and public institutions), large- and medium-sized industrial equipment (for example, measuring instruments and industrial automation equipment), precision instruments, emergency systems, and lighting systems.


Reliable

  • Built-in output isolation transformer provides good electrical isolation, and ensures high adaptability to impulse load and stable output even in the most severe load disturbance
  • Wide input voltage range (240-480 Vac) enables UPS8000-D to be applicable for the worst electrical conditions
  • Backfeed protection technology ensures the safety of the system
  • Robust inverter ensures high overload capacity: 110% overload for 60min, 125% overload for 10min, 150% overload for 1min


Efficient

  • The efficiency at online mode is higher than 94%, and for 25% load efficiency is up to 93%, as a result, UPS8000-D can save more energy than traditional UPSs in redundant configuration with low load rate
  • Intelligent hibernation technology minimizes the system power loss and helps the system operation at high efficiency at low load rate
  • Power walk-in technology boosts the proportion of UPS capacity to D.G. capacity to 1:1.1 and reduces CAPEX for customers
  • Low THDi of less than 3% minimizes the harmonic effect on the power grid


Covenient

  • Maximally, 8 UPSs can be paralleled together to satisfy different power demand
  • Cascade technology enables two independent N+X parallel systems to be connected together in emergency.
  • Module design of power unit and front maintenance design make maintenance more simple


Intelligent

  • UPS8000-D supports various types of battery and provides four different control modes according to the battery type
  • LED and graphic LCD display facilitates operation and maintenance
  • Intelligent charging and discharging management, temperature compensation, and battery intelligent hibernation technology extend the battery life by 50%

Model UPS8000-D-200K UPS8000-D-300K UPS8000-D-400K UPS8000-D-500K UPS8000-D-600K
Rated Capacity 200kVA/180kW 300kVA/270kW 400kVA/360kW 500kVA/450kW 600 kVA/540 kW
Input
Rated Voltage 380/400/415 Vac
Input Voltage Range 240-480 Vac; 360-480Vac for 100% load; 240 Vac for 65% load
Input Wiring 3Ph without neutral
Frequency Range 45-65 Hz
Total Harmonic Distortion THDi<3%
Input Power Factor 0.99
Bypass Voltage 380/400/415 Vac
Bypass Input Wiring 3Ph+N
Input Frequency ±2% (±1%-±6% adjustable)
Battery Voltage 480 Vdc
Output
Output Wiring 3Ph+N
Rated Voltage 380/400/415 Vac±1%
Frequency Same as bypass(Online mode); 50/60 Hz±0.05%(Battery mode)
Waveform Sine wave; THDv<2%(100% linear load), THDv<3%(100% non-linear load)
Output Power Factor 0.9
Output Imbalance Voltage unbalanced degree: ±1%;Phase position unbalanced degree: ±1°
Efficiency 94%
Switch Time 0 ms
Overload Capacity Three phases: 110% overload for 60 min; 125% overload for 10 min; 150% overload for 1 min;
Single phase: 200% overload for 6 s
Environment
Operation Temperature 0-40 ℃
Storage Temperature -25-70 ℃
Relative Humidity 0%-95%(Non-condensing)
Maximum Operation Altitude ≤1000 m. Above 1000 m, derating of 1% each 100 m between 1000 m and 4000 m
Audible Noise <68 dB <72 dB
Others
Height×Width×Depth (mm) 1900×1000×850 1900×1500×1000 1900×2100×1000
Weight 1000 kg 1550 kg 1720 kg 2525 kg 2700 kg
Communication Dry contacts, RS232, SNMP
Certifications TLC , CE

UPS

  • UPS8000-D-200K: 200 KVA / 180 KW; three-phase input and three-phase output
  • UPS8000-D-300K: 300 KVA / 270 KW; three-phase input and three-phase output
  • UPS8000-D-400K: 400 KVA / 360 KW; three-phase input and three-phase output
  • UPS8000-D-500K: 500 KVA / 450 KW; three-phase input and three-phase output
  • UPS8000-D-600K: 600 KVA / 540 KW; three-phase input and three-phase output
  • Choose UPS model and number according to the loads and UPS redundancy mode

Battery

  • Configure battery according to the load and the backup time.

Optional Components

Communication Card

  • Dry Contact: monitors the UPS over input and output signals
  • SNMP: monitors the UPS over the network
  • Modbus: monitors the UPS over the network

  • Component for parallel system

  • Parallel Kit: used for parallel
  • UGS: enables two single systems to be a dual-bus system
  • PSJ: enables two systems to be a whole system in emergency

  • Others

  • Cold Start Component: cold start components allow a UPS to start from the battery when there is no mains input
  • Battery Switch Box: recommend configuring battery switch box for each battery string, which can disconnect the battery from UPS when faults occur or UPS need repair
  • Battery Temperature Sensor: monitors the Temperatures of the batteries
  • Top Cable Entry Cabinet: enables cable routing from the top of the UPS8000-D