UPS5000-A Series (30-800 kVA)

Huawei UPS5000-A is an online double conversion UPS which can outputs pure sine wave with rated voltage of 380/400/415 Vac. UPS5000-A has a high efficiency of up to 96% and high power density of up to 300kVA per cabinet; all-digital control allows precise output at any input and load condition. It’s suitable to ensure continuous power supply to critical loads in large and medium datacenters.


Reliable

  • Wide input voltage range minimizing battery use: 485-305Vac for 100% load; 305-138Vac for 100%-40% load (derating linearly)
  • 5kA lightning protection design on input port to reduce lightning-related failure rate
  • Dual auxiliary power design, eliminating the single point of failure


Efficient

  • High efficiency of up to 96% for online mode, reducing power consumption effectively
  • High efficiency of up to 99% for ECO mode


Convenient

  • Rack/tower convertible for 30-120 kVA
  • High power density of up to 300kVA per cabinet, 50% footprint saving
  • High output power factor of up to 1, 25% more load driven


Intelligent

  • Flexible battery configuration: 30-40 batteries per string allow customers to get the faulty battery out instead of replacing it
  • Intelligent battery management extending battery life by 50%
  • Various communication interfaces including SNMP, dry contacts, RS485
  • NetEco network management system, supporting concentrated management to all the UPSs


Key Parameters for 30-120kVA

Rated Capacity 30kVA/30kW 40kVA/40kW 60kVA/60kW 80kVA/80kW 120kVA/120kW
Input
Input Wiring 3Ph+N+PE
Rated Voltage 380/400/415Vac
Input Voltage Range 138-485Vac
Rated Frequency 50/60Hz
Input Frequency Range 40-70Hz
Input Power Factor 0.99
THDi ≤3%
Bypass Voltage 380/400/415Vac
Bypass Frequency Range 50/60±6Hz
Battery Voltage 360-480 Vdc (the number of batteries can be selected from 30 to 40; 32 batteries in default)
Output
Output Wiring 3Ph+N+PE
Output Voltage 380/400/415Vac±1%
Output Frequency Tracking the bypass input(Online mode); 50/60Hz±0.25% (Battery mode)
THDv THDv<1%
Output Power Factor 1
Overload Capacity Inverter: 110% overload for 60min; 125% overload for 10min; 150% overload for 1min
Environment
Operating Temperature 0-40℃
Storage Temperature -40-70℃
Relative Humidity 0%-95%(No condensing)
Operating Altitude 1000m. Above 1000m, derating according to IEC62040-3
Audible Noise ≤58dB ≤64dB
Others
Height×Width×Depth (mm) 500×264×800 1020×440×850
Weight 70kg 200kg 240kg
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; Rohs, Reach, WEEE, etc.
Communication Dry Contacts, RS485, SNMP

Key Parameters for 200-800kVA

Rated Capacity 200kVA
/200kW
300kVA
/300kW
400kVA
/380kW
500kVA
/475kW
600kVA
/570kW
800kVA
/760kW
Input
Input Wiring 3Ph+N+PE
Rated Voltage 380/400/415 Vac
Voltage Range 138-485 Vac
Frequency Range 40-70 Hz
Total Harmonic Distortion ≤3%
Input Power Factor 0.99
Bypass Rated Voltage 380/400/415 Vac
Bypass Input Frequency 50/60±6 Hz
Battery Voltage 360-480 Vdc(the number of batteries can be selected from 30 to 40; 32 batteries in default)
Output
Output Wiring 3Ph+N+PE
Voltage 380/400/415 Vac±1%
Frequency Tracking the bypass input (Online Mode); 50/60 Hz±0.25% (Battery Mode)
Waveform Sine wave (THDv<1% for linear load)
Output Power Factor 1 0.95
Efficiency 96%
Overload Capacity 110% overload for 60 min; 125% overload for 10 min; 150% overload for 1 min
Environment
Operating Temperature 0-40℃
Storage Temperature -40-70℃
Relative Humidity 0%-95% (No condensing)
Maximum Operating Altitude 1000 m. Above 1000 m, derating according to IEC62040-3
Audible Noise <65 dB <67 dB <70 dB <72 dB
Others
Dimensions (H×W×D) 2000 × 600 × 850 2000 × 1200 × 850 2000 × 2400 × 850
Weight 360 kg 550 kg 900 kg 1000 kg 1100 kg 1600 kg
Certifications EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; Rohs, Reach, WEEE, etc.
Communications Dry contacts, RS485, SNMP

UPS

  • UPS5000-A series can provide 30-800kVA power supply; choose UPS model and number according to the load and UPS redundancy mode


Battery

  • Configuring battery according to the load and the battery running time


Optional Components

  • Parallel Cable
  • BSC Cable
  • Dry Contact Card
  • The dry contact card is installed in the optional card slot on the UPS and supports hot swap. The card provides six alarm dry contact outputs.


  • Battery Temperature Sensor
  • Ambient Temperature and Humidity Sensor
  • The ambient temperature and humidity sensor monitors the ambient temperature and humidity in the equipment room.


  • Battery detector
  • The battery detector monitors battery voltages and temperatures and battery string charge and discharge currents, and communicates with the PC over Modbus.


  • Battery grounding failure detector
  • The battery grounding failure detector detects battery grounding failures and sends alarm signals when the ground leakage current exceeds the specified value.